資料載入中.....
|
請使用永久網址來引用或連結此文件:
http://ir.ncue.edu.tw/ir/handle/987654321/13821
|
題名: | Analysis of Reversed Power Flow in an Open Wye-Open Delta Transformer Bank |
作者: | Chen, Tsai-Hsiang;Huang, Wei-Tzer;Cherng, Jeng-Tyan |
貢獻者: | 工業教育與技術學系 |
關鍵詞: | Distribution transformer;Open wye-open delta connection;Power quality |
日期: | 1999-11
|
上傳時間: | 2012-08-27T11:00:09Z
|
摘要: | This paper has explored the inherent characteristics of a distribution transformer with open wye-open delta connection. This connection requiring only two phases on the primary line and providing threephase four-wire service for single-phase loads and threephase loads simultaneously is therefore widely applied in the distribution systems of Taiwan Power Company. There are two single-phase transformers, named lightingleg transformer and power-leg transformer in the bank. Usually the kilovoltampere ratings of these two transformers are different. The asymmetrical structure makes its operational characteristics complicated. Usually, these two single-phase transformers do not share the load kilovoltamperes equally. Moreover, the real power is usually supplied by each of the two single-phase transformers to the loads. However, in some critical conditions, real power may be supplied to the load by only one and part of the real power may feedback to the source from the other. This state is unfavorable and should be avoided. On the basis of a detailed mathematical model of the open wye-open delta bank, this unfavorable situation is investigated in this paper. |
關聯: | IASTED International Conference on Power and Energy Systems (PES’99), November 8-10, 1999 |
顯示於類別: | [工業教育與技術學系] 會議論文
|
文件中的檔案:
檔案 |
大小 | 格式 | 瀏覽次數 |
2030101916001.pdf | 74Kb | Adobe PDF | 1191 | 檢視/開啟 |
|
在NCUEIR中所有的資料項目都受到原著作權保護.
|