題名: Analysis of Unbalance Effects on a Primary Feeder due to the Winding Connection of Distribution Transformers
作者: Wen, Kun-Li;Huang, Wei-Tzer
貢獻者: 工業教育與技術學系
關鍵詞: Primary feeder;Distribution transformer;Winding connection;Unbalance factor;Matlab/Simulink
日期: 2003-09
上傳時間: 2012-08-27T11:00:46Z
摘要: The main purpose of this paper is to discuss the unbalance effects on a primary feeder due to the various connections of distribution transformers. First of all, the common distribution transformers, such as three-phase three-wire and three-phase four-wire grounded wye-delta (Yg), ungrounded wye-delta (Y), delta-delta (), open wye-open delta (UV) and open delta-open delta (V V) connection types were modeled in Matlab/Simulink, and then the connected load with balanced and unbalanced conditions were also assumed to do simulation and analysis. Besides, the voltage and current unbalance factors were applied to be the evaluation indices to assess the degree of unbalance. The outcomes are helpful to realize the unbalance effects due to the structure and winding connection of distribution transformers, and to provide important information for the distribution engineers to select the distribution transformers at the early planning stage.
關聯: Third IASTED International Conference on Power and Energy Systems, September 3-5, 2003
顯示於類別:[工業教育與技術學系] 會議論文

文件中的檔案:

檔案 大小格式瀏覽次數
2030101916003.pdf85KbAdobe PDF501檢視/開啟


在NCUEIR中所有的資料項目都受到原著作權保護.

 


DSpace Software Copyright © 2002-2004  MIT &  Hewlett-Packard  /   Enhanced by   NTU Library IR team Copyright ©   - 回饋